language

    central africa Natural Cooling Air-Cool Chiller

    Cooling Cap.: 140-1250KW Heating Cap.: 150-1300KW Water Flow Range: 24-214.8KW Temp. Control Range: -5-20℃±1℃

    Product Description

    * Utilizes natural low-temperature cooling sources (such as air, water, soil, etc.) to provide cooling for buildings or industrial processes
    * Significantly reduces operating costs by decreasing or replacing the energy consumption of traditional compressor-based refrigeration systems

    Ideal for: Data centers, commercial buildings, industrial facilities, etc.

     

    The internal evaporator and the free-cooling coil within the unit are managed via a three-way proportional regulating valve under microprocessor automatic control, which allocates water flow between them. The control logic determines whether to activate the free-cooling coil based on the temperature difference between the outdoor air and the return water temperature of the antifreeze solution. Once the free-cooling coil is activated, the compressor-assisted refrigeration will start only if the cooling capacity from the free-cooling coil is insufficient to maintain the set leaving water temperature. If the free-cooling coil alone can achieve the required temperature, the compressor remains off. The entire unit operates automatically to achieve optimal energy efficiency.